Ethernet I/O Module with 16 bit A/12bit AI/DI/DO
Modbus TCP Data Acquisition Module(16 bit 8xSingle End AI(or 4xDifferential AI)+12bit 4xAI+2xDI+2xDO)
Product Introduction (NET-6000M Series)
NET-6000M Ethernet-based data acquisition and control modules provide I/O, data acquisitions, and networking in one module to build a cost effective, distributed monitoring and control solution for a wide variety of applications. With Ethernet-based technology, NET-6000M series modules build up a cost-effective DA&C system for building automation, environmental monitoring, and manufacturing applications. Modbus has become a standard communication, and is now the most commonly available means of connecting industrial. This makes the NET-6000M series perfect for integration with HMI, SCADA, PLC and other software systems.
Feature and benefits:
- 32 bits & 120M high speed CPU, the real time embedded OS.
 - DI can read more than 600 times/second.
 - Optocoupler isolation: Digital Input and Output.
 - RS-485: Separate isolation
 - Power or dual power(Analogue Modules): Independent isolation
 - Surge protection: 15KV
 - The analogue input: Magnetic coupling isolation and protection.
 - The input voltage can be positive and negative, each channel has TVS and ESD protection.
 - The measuring range can be shifted by software.
 - The single end and differential can be shifted by software. Single end can be changed to 16 channels by software.
 - The ID and baud rate can be adjusted by rotary button directly.
 - Enclosure: shielded metal
 - The differential sampling frequency can reach 50Hz/channel
 
Hardware Specification:
| 
 System  | 
|||
| 
 CPU  | 
 32-bit 120MIPS CPU  | 
||
| 
 Operation System  | 
 Real-Time  | 
||
| 
 Watchdog  | 
 Yes  | 
||
| 
 Communication  | 
 RS-6000M  | 
 CAN-6000T  | 
 NET-6000M  | 
| 
 
  | 
 RS485  | 
 CAN  | 
 Ethernet 10/100 Base-TX  | 
| 
 LED Display  | 
|||
| 
 Power Indicator  | 
 Red  | 
||
| 
 Run Indicator  | 
 Green  | 
||
| 
 Error Indicator  | 
 Red  | 
||
| 
 Link Indicator  | 
 Green  | 
||
| 
 Act Indicator  | 
 Yellow  | 
||
| 
 Mechanical  | 
|||
| 
 Dimensions (W x H x D)(mm)  | 
 140*110*40  | 
||
| 
 Installation  | 
 DIN-Rail mounting  | 
||
| 
 Environment  | 
|||
| 
 Operating Temperature  | 
 -20℃~+70℃  | 
||
| 
 Storage Temperature  | 
 -30℃~+80℃  | 
||
| 
 Power Requirements  | 
|||
| 
 Power Input  | 
 +9V~30V DC  | 
||
| 
 Power Consumption  | 
 <3W  | 
||
I/O Specification:
| 
 Model  | 
 NET-6088M  | 
 
  | 
|
| 
 Analog Input  | 
|||
| 
 Input Channels  | 
 8-ch Single End or 4-ch Differential  | 
||
| 
 Input Type  | 
 Single End or Differential  | 
||
| 
 Input Range  | 
 ±10V, ±5V, ±1.25V 0-20mA(External 250ohm Resistor Needed) 4-20 mA(External 250ohm Resistor Needed)  | 
||
| 
 Input Impedance  | 
 > 10M(voltage), 250 ohm (current)  | 
||
| 
 Resolution  | 
 16-bit  | 
||
| 
 Accuracy  | 
 ±0.01%  | 
||
| 
 Sampling Rate  | 
 All channels: 8 samples/sec Per channel: 1samples/sec  | 
||
| 
 Isolation  | 
 2500V  | 
||
| 
 Protection  | 
 Built-in TVS/ESD Protection ±4 kV Contact for each terminal  | 
||
| 
 Analog Output  | 
|||
| 
 Output Channels  | 
 2  | 
||
| 
 Output Range  | 
 ±10V, ±5V, 0V~5V, 0V~10V  | 
||
| 
 Resolution  | 
 12-bit  | 
||
| 
 Accuracy  | 
 ±0.1%  | 
||
| 
 Isolation  | 
 2500V  | 
||
| 
 Protection  | 
 Built-in TVS/ESD Protection ±4 kV Contact for each terminal  | 
||
| 
 Digital Input  | 
|||
| 
 Input Channels  | 
 2  | 
||
| 
 Input Type  | 
 Dry Contact  | 
 Wet Contact  | 
|
| 
 On Voltage Level  | 
 Close to GND  | 
 0V~1V DC  | 
|
| 
 Off Voltage Level  | 
 Open  | 
 3V~50V DC  | 
|
| 
 Overvoltage Protection  | 
 +70V  | 
||
| 
 Isolation  | 
 3750Vrms  | 
||
| 
 Digital Output  | 
|||
| 
 Output Channels  | 
 2  | 
||
| 
 Output Type  | 
 Sink, Open Collector(NPN)  | 
||
| 
 Load Voltage  | 
 Max 25V DC  | 
||
| 
 Max Load Current  | 
 100mA/channel  | 
||
| 
 Isolation  | 
 3750Vrms  | 
||
| 
 Input Channels  | 
 8  | 
||
Ordering Information:
1.2 Odering Information (RS-6000M Series)
| 
 Model  | 
 Description  | 
| 
 Digital I/O  | 
|
| 
 NET-6011M  | 
 Ethernet Remote I/O Module with16-ch DI  | 
| 
 NET-6012M  | 
 Ethernet Remote I/O Module with16-ch DO  | 
| 
 NET-6013M  | 
 Ethernet Remote I/O Module with 8-ch DI and 8-ch DO  | 
| 
 Relay Output  | 
|
| 
 NET-6014M  | 
 Ethernet Remote I/O Module with 5-ch Relay(Form A)  | 
| 
 NET-6015M  | 
 Ethernet Remote I/O Module with 5-ch Relay(3-ch Form A, 2-ch Form C)  | 
| 
 Analog Input  | 
|
| 
 NET-6021M  | 
 Ethernet Remote I/O Module with 12bit 16-ch Single End AI or 8-ch differential AI  | 
| 
 NET-6022M  | 
 Ethernet Remote I/O Module with 16bit 16-ch Single End AI or 8-ch differential AI  | 
| 
 Analog Output  | 
|
| 
 NET-6031M  | 
 Ethernet Remote I/O Module with 12bit 4-ch AO  | 
| 
 NET-6032M  | 
 Ethernet Remote I/O Module with 16bit 4-ch AO  | 
| 
 RTD  | 
|
| 
 NET-6041M  | 
 Ethernet Remote I/O Module with 5-ch RTD  | 
| 
 Thermocouple  | 
|
| 
 NET-6042M  | 
 Ethernet Remote I/O Module with 5-ch TC  | 
| 
 Mixed  | 
|
| 
 NET-6088  | 
 Ethernet Remote I/O Module with 16bit 8-ch Single End AI or 4-ch differential AI, 12bit 4-ch AO, 2-ch DI, 2-ch DO  |