Ethernet Remote IO Module with 16 bit 6xSingle End AI+8xDifferential AI
Modbus TCP Data Acquisition Module(16 bit 16-ch Single End Analog Input+8xDifferential Analog Input)
Product Introduction (NET-6000M Series)
NET-6000M Ethernet-based data acquisition and control modules provide I/O, data acquisitions, and networking in one module to build a cost effective, distributed monitoring and control solution for a wide variety of applications. With Ethernet-based technology, NET-6000M series modules build up a cost-effective DA&C system for building automation, environmental monitoring, and manufacturing applications. Modbus has become a standard communication, and is now the most commonly available means of connecting industrial. This makes the NET-6000M series perfect for integration with HMI, SCADA, PLC and other software systems.
Feature and benefits:
- 32 bits & 120M high speed CPU, the real time embedded OS.
- Power or dual power(Analogue Modules): Independent isolation
- Surge protection: 15KV
- The analogue input: Magnetic coupling isolation and protection.
- The input voltage can be positive and negative, each channel has TVS and ESD protection.
- The measuring range can be shifted by software.
- The single end and differential can be shifted by software. Single end can be changed to 16 channels by software.
- The ID and baud rate can be adjusted by rotary button directly.
- Enclosure: shielded metal
- The differential sampling frequency can reach 50Hz/channel
Hardware Specification:
System |
|||
CPU |
32-bit 120MIPS CPU |
||
Operation System |
Real-Time |
||
Watchdog |
Yes |
||
Communication |
RS-6000M |
CAN-6000T |
NET-6000M |
|
RS485 |
CAN |
Ethernet 10/100 Base-TX |
LED Display |
|||
Power Indicator |
Red |
||
Run Indicator |
Green |
||
Error Indicator |
Red |
||
Link Indicator |
Green |
||
Act Indicator |
Yellow |
||
Mechanical |
|||
Dimensions (W x H x D)(mm) |
140*110*40 |
||
Installation |
DIN-Rail mounting |
||
Environment |
|||
Operating Temperature |
-20℃~+70℃ |
||
Storage Temperature |
-30℃~+80℃ |
||
Power Requirements |
|||
Power Input |
+9V~30V DC |
||
Power Consumption |
<3W |
I/O Specification:
Model |
NET-6021M |
NET-6022M |
|
Analog Input |
|||
Input Channels |
16-ch Single End or 8-ch Differential |
||
Input Type |
Single End or Differential |
||
Input Range |
±10V, ±5V, ±1.25V 0-20mA(External 250ohm Resistor Needed) 4-20 mA(External 250ohm Resistor Needed) |
||
Input Impedance |
> 10M(voltage), 250 ohm (current) |
||
Resolution |
12-bit |
16-bit |
|
Accuracy |
±0.1% |
±0.01% |
|
Sampling Rate |
All channels: 16 samples/sec Per channel: 1 samples/sec |
||
Isolation |
2500V |
||
Protection |
Built-in TVS/ESD Protection ±4 kV Contact for each terminal |
Ordering Information:
1.2 Odering Information (NET-6000M Ethernet Modbus TCP Series)
Model |
Description |
Digital I/O |
|
NET-6011M |
Ethernet Remote I/O Module with16-ch DI |
NET-6012M |
Ethernet Remote I/O Module with16-ch DO |
NET-6013M |
Ethernet Remote I/O Module with 8-ch DI and 8-ch DO |
Relay Output |
|
NET-6014M |
Ethernet Remote I/O Module with 5-ch Relay(Form A) |
NET-6015M |
Ethernet Remote I/O Module with 5-ch Relay(3-ch Form A, 2-ch Form C) |
Analog Input |
|
NET-6021M |
Ethernet Remote I/O Module with 12bit 16-ch Single End AI or 8-ch differential AI |
NET-6022M |
Ethernet Remote I/O Module with 16bit 16-ch Single End AI or 8-ch differential AI |
Analog Output |
|
NET-6031M |
Ethernet Remote I/O Module with 12bit 4-ch AO |
NET-6032M |
Ethernet Remote I/O Module with 16bit 4-ch AO |
RTD |
|
NET-6041M |
Ethernet Remote I/O Module with 5-ch RTD |
Thermocouple |
|
NET-6042M |
Ethernet Remote I/O Module with 5-ch TC |
Mixed |
|
NET-6088 |
Ethernet Remote I/O Module with 16bit 8-ch Single End AI or 4-ch differential AI, 12bit 4-ch AO, 2-ch DI, 2-ch DO |